Cohen Coon Tuning Method
  1. Under Manual mode, wait until the process is at steady state.
  2. Next, introduce a step change in the input.
  3. Based on the output, obtain an approximate first order process with a time constant t delayed by tDEL units from when the input step was introduced.

  4.  

     

    The values of t and tDEL can be obtained by first recording the following time instances:
     
     

    t0 = time when input step was initiated
    t2 = time when half point occurs
    t3 = time when 63.2% point occurs


  5. From the measurements based on the step test: t0, t2, t3, A and B, evaluate the following process parameters:

  6.  

     
     

    t1 = (t2 - ln(2) t3)/(1 - ln(2))

    t = t3 - t1

    tDEL = t1 - t0

    K = B/A


  7. Based on the parameters K, t and tDEL, the following formulas prescribe the controller parameters Kc, tI and tD:





( Use the BACK button of your browser to return to a currently running PID tuning simulation, otherwise click here to initiate a PID tuning simulation.)